Wireless Differential Pressure Transmitter | PM450-DS
The PM450-DS Series Wireless Differential Pressure Transmitter provides precise, cable-free differential pressure and flow monitoring across air, liquid, and gas systems in remote or industrial environments. Powered by an ultra-high-capacity 38Ah internal lithium battery, this unit eliminates complex field wiring and signal cable runs. The PM450-DS supports multi-protocol IoT communications—including 4G, NB-IoT, LoRa, and LoRaWAN—and can be configured for standard differential pressure or dual differential pressure/temperature monitoring (Code DS). Built with dual 316L stainless steel process ports, an integrated HD LCD panel, and explosion-proof IP67 enclosure, it is designed for filter monitoring, cleanroom pressure control, and pipeline differential flow measurement.
-
Cable-Free Differential Pressure: High-precision dual-port pressure sensing without field signal wiring or external power supply lines.
-
Ultra-Long Battery Life: High-capacity 3.6V / 38Ah lithium battery yields 1 to 3 years of continuous field operation.
-
Dual Parameter Monitoring (Code DS): Measures differential pressure alongside process temperature over a single wireless connection.
-
Multi-Network IoT Protocol Options: Seamless integration into cloud platforms or local SCADA systems via 4G (TCP/MQTT), NB-IoT, LoRa, or LoRaWAN.
Description
Efficient Remote Differential Pressure & Flow Monitoring
Monitoring differential pressure across filters, pumps, heat exchangers, or orifice plates in vast industrial plants and remote pipeline networks typically requires extensive cabling and conduit installation. The PM450-DS Wireless Differential Pressure Transmitter replaces traditional wired instrumentation with micro-power wireless IoT communication, drastically lowering installation labor and infrastructure costs.
Engineered with dual 316L stainless steel wetted ports and advanced digital sensing elements, the PM450-DS calculates real-time differential pressure values and uploads readings to cloud platforms (such as MQTT, TCP, Mobile OneNET, or LwM2M) or local Modbus gateways.
Dual-Parameter Sensing & Clear Local Display
The PM450-DS is available as a dedicated differential pressure unit (Code D) or with integrated temperature monitoring (Code DS). The dual-parameter DS option measures media temperature while simultaneously recording differential pressure, eliminating the need to install additional temperature transmitters on the line.
The front panel features a 5-digit HD LCD display showing engineering units (kPa, bar, psi, MPa), differential values, signal strength, battery voltage, and channel parameters. Integrated over-range flashing warnings and customizable alarm thresholds provide fast local and remote diagnostic alerts during line blockages or filter overload.
Versatile Wireless Communication Architecture
To match your network setup, the PM450-DS offers multiple communication options:
-
4G LTE (TCP/MQTT): Direct long-distance cellular data transmission to custom cloud servers or SCADA platforms with Bluetooth and USB setup capabilities.
-
NB-IoT: Ultra-low power cellular transmission over LwM2M, TCP, or MQTT protocols.
-
LoRa / LoRaWAN: Long-range, license-free wireless connection (410–441 MHz, 850–950 MHz) designed for private facility networks up to 1000m line-of-sight distance.
Features
-
High Static Pressure Resistance: Micro-machined dual-port sensor construction handles differential pressure accurately across fluctuating system pressures.
-
Micro-Power Sleep Mode: Ultra-low standby consumption (<20uA) ensures stable battery performance up to 3 years.
-
Dual-Parameter Capabilities: Select Code D for differential pressure or Code DS for combined differential pressure and temperature monitoring.
-
Robust Construction: 316L stainless steel process ports and explosion-proof enclosure (1G Ex ia da op is IIC T4 Ga) with IP65/IP67 rating.
-
Flexible Sampling & Upload Rates: Report intervals configurable from 30 seconds to 24 hours to match process criticalities.
-
Convenient Magnetic Reset: Magnetic key-press and button wake-up functions allow quick field configuration, testing, and gateway resynchronization.
Specification
| Technical Parameter | Specification Value |
| Model |
PM450-DS Wireless Differential Pressure Transmitter |
| Measurement Parameters |
Differential Pressure (Code D) OR Differential Pressure & Temperature (Code DS) |
| Differential Pressure Ranges |
0…10 kPa to 0…2.5 MPa (Custom ranges available) |
| Temperature Range |
-30°C to +300°C (Process dependent) |
| Accuracy |
0.25% F.S. (Typical) / 0.1% F.S. (Custom) |
| Long-Term Stability |
±0.1% F.S./year (Typical) |
| Display |
5-Digit HD LCD displaying DP value, units, signal, and battery capacity |
| Power Supply |
3.6 VDC Lithium-ion battery (38000 mAh capacity) |
| Battery Life |
1 to 3 years (Interval dependent) |
| Wireless Protocols |
4G (TCP/MQTT), NB-IoT, LoRa, LoRaWAN, Zigbee |
| Process Connection |
Standard differential pressure ports (1/4 NPT, G1/4, or custom manifold mounts) |
| Wetted Material |
316L Stainless Steel |
| Protection Rating |
IP65 / IP67 |
| Explosion-Proof Rating |
1G Ex ia da op is IIC T4 Ga |
| Operating Temperature |
-20°C to +75°C (Ambient) |
FAQ
Q: What is the main difference between Code D and Code DS on the PM450-DS?
A: Code D configures the instrument as a standard wireless differential pressure transmitter. Code DS includes an integrated temperature sensor probe, enabling simultaneous monitoring and wireless transmission of both differential pressure and media temperature.
Q: Where is a wireless differential pressure transmitter typically used?
A: Common applications include monitoring pressure drops across liquid/gas filters, measuring liquid levels in pressurized sealed tanks, monitoring cleanroom differential pressures, and estimating flow rates across orifice plates or Venturi tubes without running cabling.
Q: Can I adjust data reporting frequency to extend battery life?
A: Yes. Transmission intervals can be set anywhere from 30 seconds up to 24 hours via Bluetooth mobile app, USB PC connection, or cloud server commands. Lowering upload frequencies significantly prolongs the internal 38Ah lithium battery life.
Q: How does the PM450-DS connect to my SCADA or PLC network?
A: For cellular versions (4G / NB-IoT), the device posts data directly to standard cloud servers via MQTT or TCP. For LoRa or LoRaWAN versions, data transmits to a wireless gateway, which converts signals to standard RS485 Modbus RTU/TCP or Ethernet output for direct PLC/SCADA integration.