Compact Pressure Transmitter | 4-20mA & 0-10V for HVAC, VFDs & Air Compressors | P10

High-Reliability Compact Pressure Transmitter for HVAC, VFD Control & Air Compressors

The P10 Series is an industrial-grade ceramic pressure sensor engineered for air, water, refrigeration, and hydraulic systems. Featuring robust EMI/RFI shielding and wide output options (4-20mA, 0-10V, 0.5-4.5V), it integrates seamlessly with Variable Frequency Drives (VFDs), PLCs, and Building Management Systems (BMS).

  • Standard Signal Options: 2-wire 4-20mA, 3-wire 0-10V, 0-5V, or 0.5-4.5V ratiometric.

  • Multiple Connectors: Hirschmann DIN43650, M12 4-Pin, Packard, or direct-sealed lead cable (P91 configuration).

  • Durable Sensing Core: Ceramic cell with automatic temperature compensation and IP65–IP67 protection.

  • Versatile Pressure Ranges: Gauge and negative pressure options from -1 bar up to 600 bar.

Description

Engineered for Seamless System Integration

In industrial automation and HVAC systems, a pressure sensor is only as good as its integration with your motor drive or control unit. The P10 series provides exact signal matching for constant-pressure pump controls, air compressors, and ventilation systems.

Key Application Areas

  • VFD Constant Pressure Control: Connect the 4-20mA or 0-10V output directly to your VFD PID feedback loops for energy-efficient water pumping and fan velocity control.

  • Air Compressors & HVAC Ducts: Monitor pneumatic pressure lines, refrigeration circuits, and HVAC air loops with stable ceramic sensing technology.

  • Hydraulics & Process Lines: High-pressure variants up to 600 bar handle harsh industrial pressure spikes with high EMI/RFI immunity.

Configuration Options (P10 vs. P91 Pre-Wired)

To simplify field service and installation, choose between two primary connection profiles:

  1. P10 Plug Series: Uses detachable Hirschmann DIN43650 or M12 4-Pin connectors for quick replacement and field maintenance.

  2. P91 Cable Series: Features a direct-sealed cable outlet (standard 40cm or custom lengths) ideal for compact OEM machinery and tight compressor enclosures.


Features

  • Ceramic Sensing Cell: Highly resistant to mechanical wear, cavitation, and aggressive process media.

  • Broad Electrical Compatibility: Configurable in 4-20mA (10-30V DC), 0-10V (15-30V DC), and 0.5-4.5V ratiometric (5V DC).

  • Industrial Shielding: Advanced internal electronics guard against electrical noise and radio frequency interference (EMI/RFI).

  • Flexible Process Ports: Available in standard G1/4 male, G1/2 male, 1/4 NPT male/female, 1/8 NPT, and 7/16-20 UNF.

  • Environmental Protection: IP65 rating on standard DIN connectors and up to IP67 on direct-cable and M12 configurations.

  • Automatic Thermal Compensation: Maintains reliable accuracy across working temperature swings.


 

Specification

Parameter Technical Details
Pressure Ranges -1…0…1 bar up to 0…600 bar (Gauge / Negative)
Output Signals 4-20mA (2-wire), 0-5V, 0-10V, 0.5-4.5V Ratiometric (3-wire)
Power Supply 10-30V DC (for 4-20mA), 15-30V DC (for 0-10V), 5V DC (Ratiometric)
Accuracy Standard: ≤ ±1.0% F.S.
Long-Term Stability 0.2% F.S. ±0.05% / year
Operating Temperature Medium: -30°C to +105°C
Temperature Compensation 0°C to +50°C (≤ 2% F.S. thermal drift)
Wetted Materials 304 Stainless Steel, Ceramic Diaphragm, FKM / CR / HNBR O-Rings
Electrical Connectors DIN43650 Hirschmann, M12 4-Pin, Packard 3-Pin, Direct Sealed Cable (P91 style)
Process Connections G1/4″ male, G1/2″ male, 1/4″ NPT male/female, 1/8″ NPT male, 7/16-20 UNF
Ingress Protection IP65 (DIN / Packard) / IP67 (M12 / Direct Cable)

FAQ

Q: Which output signal should I select for a VFD pump control setup?

A: If your Variable Frequency Drive (VFD) is installed more than a few meters away from the sensor, choose 4-20mA (2-wire) to eliminate signal voltage drop. For direct control panel wiring or Building Management Systems (BMS) that default to voltage loops, select 0-10V.

Q: What is the difference between the P10 standard model and the P91 configuration?

A: The P10 uses quick-disconnect plug bodies (such as Hirschmann DIN or M12) for fast field replacement. The P91 option replaces the plug housing with a pre-wired, direct-sealed cable outlet for space-constrained machine OEM applications.

Q: Can this sensor handle water pressure spikes or hydraulic shock?

A: Yes. The ceramic diaphragm offers strong burst and overpressure resistance. For systems prone to extreme pressure hammer (such as fast-closing solenoid valves), installing a simple pressure snubber upstream of the sensor port is recommended.

Q: Is this sensor compatible with air compressors and refrigeration media?

A: Absolutely. The P10 features inert ceramic sensing elements and fluorine rubber seals (FKM/HNBR) compatible with non-corrosive gases, air, water, synthetic oils, and standard refrigerants.

Q: Does Longvista provide technical support for wiring and parameter setup?

A: Yes. As a Swiss industrial automation specialist, Longvista offers direct wiring guidance and setup advice for pairing pressure transmitters with VFDs and controllers.


Datasheet